Descripción
834 total views, 1 views today
Product range
|
Control relays easyRelay | ||
Basic function
|
easy500 | ||
Description
|
Stand alone customized laser inscription or delivery with user program possible with EASY-COMBINATION-* product (article No. 2010781) |
||
Inputs
|
|||
Digital input count
|
digital: 8 digital: 8; of which can be used as analog: 2 |
||
Digital
|
8 | ||
of which can be used as analog
|
2 | ||
Outputs
|
|||
Type
|
Relay | ||
Quantity of outputs
|
Relays: 4 | ||
Outputs
|
Number | 4 | |
Relay 10 A (UL)
|
4 | ||
Additional features
|
|||
Display
|
with display, with keypad | ||
Display & keypad
|
✔ | ||
Supply voltage
|
24 V DC | ||
Software
|
EASY-SOFT-BASIC/-PRO |
General | |||
Standards
|
EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27 | ||
Dimensions (W x H x D)
|
mm | 71.5 x 90 x 58 (4 PE) | |
Weight
|
kg | 0.2 | |
Mounting
|
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories) | ||
Terminal capacities | |||
Solid
|
mm2 | 0.2/4 (AWG 22 – 12) | |
Flexible with ferrule
|
mm2 | 0.2/2.5 (AWG 22 – 12) | |
Standard screwdriver
|
mm | 3.5 x 0.8 | |
Max. tightening torque
|
Nm | 0.6 | |
Climatic environmental conditions | |||
Operating ambient temperature
|
°C | In accordance with IEC 60068-2-1, -25 – +55 | |
Condensation
|
Take appropriate measures to prevent condensation | ||
LCD display (clearly legible)
|
°C | 0 – 55 | |
Storage
|
ϑ | °C | -40 – +70 |
relative humidity
|
% | in accordance with IEC 60068-2-30, IEC 60068-2-78 5 – 95 |
|
Air pressure (operation)
|
hPa | 795 – 1080 | |
Ambient conditions, mechanical | |||
Protection type (IEC/EN 60529, EN50178, VBG 4)
|
IP20 | ||
Vibrations
|
3,5 mm / 1 g | Hz | In accordance with IEC 60068-2-6 constant amplitude 0.15 mm: 10 – 57 constant acceleration 2 g: 57 – 150 |
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
|
Impacts | 18 | |
Drop to IEC/EN 60068-2-31
|
Drop height | mm | 50 |
Free fall, packaged (IEC/EN 60068-2-32)
|
m | 1 | |
Mounting position
|
Vertical or horizontal | ||
Electromagnetic compatibility (EMC) | |||
Overvoltage category/pollution degree
|
III/2 | ||
Electrostatic discharge (ESD)
|
|||
applied standard
|
according to IEC EN 61000-4-2 | ||
Air discharge
|
kV | 8 | |
Contact discharge
|
kV | 6 | |
Electromagnetic fields (RFI) to IEC EN 61000-4-3
|
V/m | 10 | |
Radio interference suppression
|
EN 55011 Class B, EN 55022 Class B | ||
Burst
|
kV | according to IEC/EN 61000-4-4 Supply cables: 2 Signal cables: 2 |
|
power pulses (Surge)
|
according to IEC/EN 61000-4-5 1 kV (supply cables, symmetrical) |
||
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
|
V | 10 | |
Insulation resistance | |||
Clearance in air and creepage distances
|
EN 50178, UL 508, CSA C22.2, No. 142 | ||
Insulation resistance
|
EN 50178 | ||
Repetition accuracy of timing relays | |||
Accuracy of timing relays (of values)
|
% | ± 1 | |
Resolution
|
|||
Range “S”
|
ms | 10 | |
Range “M:S”
|
s | 1 | |
Range “H:M”
|
min | 1 | |
Retentive memory | |||
Write cycles of the retentive memory
|
1000000 (10⁶) | ||
Power supply | |||
Rated operational voltage
|
Ue | V | 24 DC (-15/+20%) |
Permissible range
|
Ue | 20.4 – 28.8 V DC | |
Residual ripple
|
% | ≦ 5 | |
Input current
|
normally 80 mA at Ue | ||
Voltage dips
|
ms | ≤ In accordance with IEC 61131-2 ≤ 10 |
|
Fuse
|
A | ≧ 1A (T) | |
Power loss
|
P | W | Normally 2 |
Digital inputs 24 V DC | |||
Number
|
8 | ||
Inputs can be used as analog inputs
|
2 (I7,I8) | ||
Status Display
|
LCD-Display | ||
Potential isolation
|
from power supply: no between digital inputs: no from the outputs: yes to interface/memory card: no |
||
Rated operational voltage
|
Ue | V DC | 24 |
Input voltage
|
V DC | Signal 0: ≦ 5 (I1 – I8) Signal 1: ≧ 15 (I1 – I6), ≧ 8 (I7, I8) |
|
Input current at signal 1
|
mA | I1 – I6: 3.3 (at 24 V DC) I7, I8: 2.2 (at 24 V DC) |
|
Deceleration time
|
ms | 20 (0 -> 1/1 -> 0, Debounce ON) normally 0.25 (0 -> 1, Debounce OFF, I1 – I8) |
|
Cable length
|
m | 100 (unshielded) | |
Frequency counter
|
|||
Number
|
2 (I3, I4) | ||
Counter frequency
|
kHz | ≦ 1 | |
Pulse shape
|
Square | ||
Pulse pause ratio
|
1:1 | ||
Cable length
|
m | ≦ 20 (screened) | |
Rapid counter inputs
|
|||
Number
|
2 (I1, I2) | ||
Cable length
|
m | ≦ 20 (screened) | |
Counter frequency
|
kHz | < 1 | |
Pulse shape
|
Square | ||
Pulse pause ratio
|
1:1 | ||
Digital inputs 24 V DC | |||
Status Display
|
LCD-Display | ||
Analog inputs | |||
Number
|
2 (I7, I8) | ||
Potential isolation
|
from power supply: no between digital inputs: no from the outputs: yes to interface/memory card: no |
||
Input type
|
DC voltage | ||
Signal range
|
0-10 V DC | ||
Resolution
|
0.01 V analog 0.01 V digital 10 Bit (value 0 – 1023) |
||
Input impedance
|
kΩ | 11.2 | |
Accuracy of actual value
|
|||
Two EASY devices
|
% | ± 3 | |
Within a single device
|
% | ± 2, (I7, I8, I11, I12) ± 0.12 V | |
Conversion time, analog/digital
|
ms | Input delay ON: 20; Input delay OFF: each cycle time | |
Input current
|
mA | < 1 | |
Cable length
|
m | ≦ 30, screened | |
Relay outputs | |||
Number
|
4 | ||
Outputs in groups of
|
1 | ||
Parallel switching of outputs for increased output
|
Not permissible | ||
Protection of an output relay
|
Miniature circuit-breaker B16 or fuse 8 A (slow) | ||
Potential isolation
|
from power supply: yes From the inputs: yes Safe isolation according to EN 50178: 300 V AC Basic isolation: 600 V AC |
||
Lifespan, mechanical
|
Operations | x 106 | 10 |
Contacts
|
|||
Conventional thermal current (10 A UL)
|
A | 8 | |
Recommended for load: 12 V AC/DC
|
mA | > 500 | |
Short-circuit-proof cos ϕ = 1, characteristic B16 at 600 A
|
A | 16 | |
Short-circuit-proof cos ϕ = 0.5 to 0.7, characteristic B16 at 900 A
|
A | 16 | |
Rated impulse withstand voltage Uimp of contact coil
|
kV | 6 | |
Rated operational voltage
|
Ue | V AC | 250 |
Rated insulation voltage
|
Ui | V AC | 250 |
Safe isolation according to EN 50178
|
V AC | 300 between coil and contact 300 between two contacts |
|
Making capacity
|
|||
AC–-15, 250 V AC, 3 A (600 ops./h)
|
Operations | 300000 | |
DC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h)
|
Operations | 200000 | |
Breaking capacity
|
|||
AC-15, 250 V AC, 3 A (600 Ops./h)
|
Operations | 300000 | |
DC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 S/h)
|
Operations | 200000 | |
Filament bulb load
|
|||
1000 W at 230/240 V AC
|
Operations | 25000 | |
500 W at 115/120 V AC
|
Operations | 25000 | |
Fluorescent lamp load
|
|||
Fluorescent lamp load 10 x 58 W at 230/240 V AC
|
|||
With upstream electrical device
|
Operations | 25000 | |
Uncompensated
|
Operations | 25000 | |
Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated
|
Operations | 25000 | |
Switching frequency
|
|||
Mechanical operations
|
x 106 | 10 | |
Switching frequency
|
Hz | 10 | |
Resistive load/lamp load
|
Hz | 2 | |
Inductive load
|
Hz | 0.5 | |
UL/CSA
|
|||
Uninterrupted current at 240 V AC
|
A | 10 | |
Uninterrupted current at 24 V DC
|
A | 8 | |
AC
|
|||
Control Circuit Rating Codes (utilization category)
|
B 300 Light Pilot Duty | ||
Max. rated operational voltage
|
V AC | 300 | |
max. thermal continuous current cos ϕ = 1 at B 300
|
A | 5 | |
max. make/break cos ϕ ≠ capacity 1 at B 300
|
VA | 3600/360 | |
DC
|
|||
Control Circuit Rating Codes (utilization category)
|
R 300 Light Pilot Duty | ||
Max. rated operational voltage
|
V DC | 300 | |
Max. thermal uninterrupted current at R 300
|
A | 1 | |
Max. make/break capacity at R 300
|
VA | 28/28 | |
Supply voltage UAux | |||
Power loss
|
P | W | 2 |
Product Standards | IEC/EN see Technical Data; UL 508; CSA C22.2 No. 142-M1987; CSA C22.2 No. 213-M1987; CE marking | ||
UL File No. | E135462 | ||
UL Category Control No. | NRAQ | ||
CSA File No. | 012528 | ||
CSA Class No. | 2252-01 + 2258-02 | ||
North America Certification | UL listed, CSA certified | ||
Degree of Protection | IEC: IP20, UL/CSA Type: – |
Valoraciones