Standards
|
|
|
EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27 |
Dimensions (W x H x D)
|
|
mm |
107.5 x 90 x 72 (6 PE) |
Weight
|
|
kg |
0.3 |
Mounting
|
|
|
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories) |
Solid
|
|
mm2 |
0.2/4 (AWG 22 – 12) |
Flexible with ferrule
|
|
mm2 |
0.2/2.5 (AWG 22 – 12) |
Standard screwdriver
|
|
mm |
3.5 x 0.8 |
Max. tightening torque
|
|
Nm |
0.6 |
Operating ambient temperature
|
|
°C |
In accordance with IEC 60068-2-1, -25 – +55 |
Condensation
|
|
|
Take appropriate measures to prevent condensation |
Storage
|
ϑ |
°C |
In accordance with IEC 60068-2-1, -2, -14
-40 – +70 |
relative humidity
|
|
% |
in accordance with IEC 60068-2-30, IEC 60068-2-78
5 – 95 |
Air pressure (operation)
|
|
hPa |
795 – 1080 |
Protection type (IEC/EN 60529, EN50178, VBG 4)
|
|
|
IP20 |
Vibrations
|
3,5 mm / 1 g |
Hz |
In accordance with IEC 60068-2-6
constant amplitude 0.15 mm: 10 – 57
constant acceleration 2 g: 57 – 150 |
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
|
|
Impacts |
18 |
Drop to IEC/EN 60068-2-31
|
Drop height |
mm |
50 |
Free fall, packaged (IEC/EN 60068-2-32)
|
|
m |
1 |
Mounting position
|
|
|
Vertical or horizontal |
Overvoltage category/pollution degree
|
|
|
III/2 |
Electrostatic discharge (ESD)
|
|
|
|
applied standard
|
|
|
according to IEC EN 61000-4-2 |
Air discharge
|
|
kV |
8 |
Contact discharge
|
|
kV |
6 |
Electromagnetic fields (RFI) to IEC EN 61000-4-3
|
|
V/m |
0.8 – 1.0 GHz: 10
1.4 – 2 GHz: 3
2.0 – 2.7 GHz: 1 |
Radio interference suppression
|
|
|
EN 55011 Class B |
Burst
|
|
kV |
according to IEC/EN 61000-4-4 |
power pulses (Surge)
|
|
|
according to IEC/EN 61000-4-5
1 kV (supply cables, symmetrical) |
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
|
|
V |
10 |
Clearance in air and creepage distances
|
|
|
EN 50178, UL 508, CSA C22.2, No. 142 |
Insulation resistance
|
|
|
EN 50178 |
Back-up of real-time clock
|
|
|
  |
|
|
|
① Backup time (hours) with fully charged double layer capacitor
② Service life (years) |
Accuracy of real-time clock to inputs
|
|
s/day |
typ. ± 2 (± 0.2 h⁄Year) |
|
|
|
depending on ambient air temperature fluctuations of up to ± 5 s/day (± 0.5 h⁄year) are possible |
Accuracy of timing relays (of values)
|
|
% |
± 0.02 |
Resolution
|
|
|
|
Range “S”
|
|
ms |
5 |
Range “M:S”
|
|
s |
1 |
Range “H:M”
|
|
min |
1 |
Write cycles of the retentive memory
|
|
|
1012 (read⁄write cycles) |
Rated operational voltage
|
Ue |
V |
24 DC (-15/+20%) |
Permissible range
|
Ue |
|
20.4 – 28.8 V DC |
Residual ripple
|
|
% |
≦ 5 |
Siemens MPI, (optional)
|
|
|
yes |
Input current
|
|
|
140 mA at Ue |
Voltage dips
|
|
ms |
≤ In accordance with IEC 61131-2
≤ 20 |
Fuse
|
|
A |
≧ 1A (T) |
Power loss
|
P |
W |
Normally 3.4 |
Number
|
|
|
12 |
Inputs can be used as analog inputs
|
|
|
4 (I7, I8, I11, I12) |
Potential isolation
|
|
|
from power supply: no
between digital inputs: no
from the outputs: yes
to interface/memory card: no
to easyLink: no
to easyNet: yes |
Rated operational voltage
|
Ue |
V DC |
24 |
Input voltage
|
|
V DC |
Signal 0: ≦ 5 (I1 – I6, I9, I10, ≦ 8 (I7, I8, I11, I12)
Signal 1: ≧ 15 (I1 – I6, I9, I10), ≧ 8 (I7, I8, I11, I12) |
Input current at signal 1
|
|
mA |
I1 – I6, I9, I10: 3.3 (at 24 V DC)
I7, I8, I11, I12: 2.2 (at 24 V DC) |
Deceleration time
|
|
ms |
20 (0 -> 1/1 -> 0, Debounce ON)
normally 0.025 (0 -> 1/1 -> 0, Debounce OFF, I1 – I4)
normally 0.25 (0 -> 1/1 -> 0, Debounce OFF, I5, I6, I9, I10)
normally 0.15 (0 -> 1/1 -> 0, Debounce OFF, I7, I8, I11, I12) |
Cable length
|
|
m |
100 (unshielded) |
Frequency counter
|
|
|
|
Number
|
|
|
4 (I1, I2, I3, I4) |
Counter frequency
|
|
kHz |
≦ 5 |
Pulse shape
|
|
|
Square |
Pulse pause ratio
|
|
|
1:1 |
Cable length
|
|
m |
≦ 20 (screened) |
Incremental counter
|
|
|
|
Number of counter inputs
|
|
|
2 (I1 + I2, I3 + I4) |
Counter frequency
|
|
kHz |
≦ 3 |
Pulse shape
|
|
|
Square |
Signal offset
|
|
|
90° |
Pulse pause ratio
|
|
|
1:1 |
Rapid counter inputs
|
|
|
|
Number
|
|
|
4 (I1, I2, I3, I4) |
Cable length
|
|
m |
≦ 20 (screened) |
Counter frequency
|
|
kHz |
< 5 |
Pulse shape
|
|
|
Square |
Pulse pause ratio
|
|
|
1:1 |
Number
|
|
|
4 (I7, I8, I11, I12) |
Potential isolation
|
|
|
from power supply: no
between digital inputs: no
from the outputs: yes
to interface/memory card: no
to easyLink: no
to easyNet: yes |
Input type
|
|
|
DC voltage |
Signal range
|
|
|
0-10 V DC |
Resolution
|
|
|
0.01 V analog
0.01 V digital
10 Bit (value 0 – 1023) |
Input impedance
|
|
kΩ |
11.2 |
Accuracy of actual value
|
|
|
|
Two EASY devices
|
|
% |
± 3 |
Within a single device
|
|
% |
± 2, (I7, I8, I11, I12) ± 0.12 V |
Conversion time, analog/digital
|
|
ms |
each CPU cycle |
Input current
|
|
mA |
< 1 |
Cable length
|
|
m |
≦ 30, screened |
Number
|
|
|
8 |
Rated operational voltage
|
Ue |
V DC |
24 |
Permissible range
|
Ue |
|
20.4 – 28.8 V DC |
Residual ripple
|
|
% |
5 |
Supply current
|
|
mA |
Norm./max. 18/32 at signal 0
24/44 at signal 1 |
Siemens MPI, (optional)
|
|
|
yes (Notice: A short-circuit will result if 0 V or earth is applied to the outputs in the event that the supply voltage is connected to the wrong poles.) |
Potential isolation
|
|
|
from power supply: yes
From the inputs: yes
between digital inputs: no
to the interface: yes
to easyLink: yes
to easyNet: yes |
Rated operational current at signal „1” DC per channel
|
Ie |
A |
max. 0.5 |
Lamp load without Rv per channel
|
|
W |
3 (Q1 – Q4)
5 (Q5 – Q8) |
Residual current on 0 signal per channel
|
|
mA |
< 0.1 |
Max. output voltage
|
|
V |
2.5 (signal 0 at external load < 10 MΩ)
U = Ue – 1 V (signal 1 at Ie = 0.5 A) |
Short-circuit protection
|
|
|
Yes, electronic (Q1 – Q4), thermal (Q5 – Q8) |
Short-circuit tripping current for Ra ≦ 10 mΩ
|
|
A |
0.7 ≦ Ie ≦ 2 per output
depending on number of active channels and their load |
Total short-circuit current
|
|
A |
8 |
Peak short-circuit current
|
|
A |
16 |
Thermal cutout
|
|
|
Yes |
Max. operating frequency with constant resistive load
|
|
Operations/h |
40000 |
Parallel connection of outputs
|
|
|
|
With resistive load, inductive load with external suppressor circuit, combination within a group
|
|
|
Group 1: Q1 to Q4
Group 2: Q5 – Q8 |
Number of outputs
|
max. |
|
4 |
Max. total current
|
|
A |
Group 1: Q1 – Q4 |
Inductive load to EN 60947-5-1
|
|
|
|
Without external suppressor circuit
|
|
|
|
T0.95 = 1 ms, R = 48 Ω, L = 16 mH
|
|
|
|
Utilization factor
|
|
g |
0.25 |
Duty factor
|
|
% DF |
100 |
Max. switching frequency f = 0.5 Hz (max. DF = 50 %)
|
|
Operations |
1500 |
DC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 H
|
|
|
|
Utilization factor
|
|
g |
0.25 |
Duty factor
|
|
% DF |
100 |
Max. switching frequency f = 0.5 Hz (max. DF = 50 %)
|
|
Operations |
1500 |
T0.95 = 15 ms, R = 48 Ω, L = 0.24 H
|
|
|
|
Utilization factor
|
|
g |
0.25 |
Duty factor
|
|
% DF |
100 |
Max. switching frequency f = 0.5 Hz (max. DF = 50 %)
|
|
Operations |
1500 |
With external suppressor circuit
|
|
|
|
Utilization factor
|
|
g |
1 |
Duty factor
|
|
% DF |
100 |
Max. switching frequency, max. duty factor
|
|
Operations |
Depending on the suppressor circuit |
Power loss
|
P |
W |
3.4 |
Data transfer rate/distance
|
|
|
1000 KBit/s, 6 m
500 KBit/s, 25 m
250 Kbit/s, 40 m
125 Kbit/s, 300 m
50 KBit/s, 300 m
20 KBit/s, 700 m
10 KBit/s, 1000 m
Lengths from 40 m can be obtained only with cables with reinforced cross-section and terminal adapter. |
Potential isolation
|
|
|
from power supply POW: yes
From the inputs: yes
from the outputs: yes
to easyLink: yes
to the interface: yes |
Bus termination (first and last station)
|
|
|
yes |
Terminal types
|
|
|
RJ45, 8-polig |
Terminal capacity
|
|
|
up to 1000 m, < 16 mΩ/m: 1.5 (AWG: 16)
up to 600 m, < 26 mΩ/m: 0.75 – 0.8 (AWG: 18)
up to 600 m, < 26 mΩ/m: 0.5 – 0.6 (AWG: 20, 19)
up to 400 m, < 40 mΩ/m: 0.34 – 0.5 (AWG: 22, 21, 20)
up to 250 m, < 60 mΩ/m: 0.25 – 0.34 (AWG: 23, 22)
up to 175 m, < 70 mΩ/m: 0.13 (AWG: 26)
up to 40 m, < 140 mΩ/m: 1.5 (AWG: 16) |
Valoraciones