Descripción
Product range
|
Contactors | ||
Application
|
Contactors for Motors | ||
Subrange
|
Contactors up to 170 A, 3 pole | ||
Utilization category
|
AC-1: Non-inductive or slightly inductive loads, resistance furnaces NAC-3: Normal AC induction motors: starting, switch off during running AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
||
Notes
|
Also suitable for motors with efficiency class IE3. IE3-ready devices are identified by the logo on their packaging. |
||
Connection technique
|
Screw terminals | ||
Number of poles
|
3 pole | ||
Rated operational current
|
|||
AC-3
|
|||
380 V 400 V
|
Ie | A | 18 |
AC-1
|
|||
Conventional free air thermal current, 3 pole, 50 – 60 Hz
|
|||
Open
|
|||
at 40 °C
|
Ith =Ie | A | 40 |
enclosed
|
Ith | A | 32 |
Conventional free air thermal current, 1 pole
|
|||
open
|
Ith | A | 88 |
enclosed
|
Ith | A | 80 |
Max. rating for three-phase motors, 50 – 60 Hz
|
|||
AC-3
|
|||
220 V 230 V
|
P | kW | 5 |
380 V 400 V
|
P | kW | 7.5 |
660 V 690 V
|
P | kW | 11 |
AC-4
|
|||
220 V 230 V
|
P | kW | 2.5 |
380 V 400 V
|
P | kW | 4.5 |
660 V 690 V
|
P | kW | 6.5 |
Contacts
|
|||
N/O = Normally open
|
1 N/O | ||
Instructions
|
Contacts to EN 50 012. | ||
Can be combined with auxiliary contact
|
DILM32-XHI.. DILA-XHI(V).. |
||
Voltage AC/DC
|
AC operation |
Valoraciones
No hay valoraciones aún.