sign verification as per IEC/EN 61439(Hide features)
Technical data for design verification
Rated operational current for specified heat dissipation
In A 0
Heat dissipation per pole, current-dependent
Pvid W 0
Equipment heat dissipation, current-dependent
Pvid W 0
Static heat dissipation, non-current-dependent
Pvs W 0.1
Heat dissipation capacity
Pdiss W 0
Operating ambient temperature min.
°C -25
Operating ambient temperature max.
°C 55
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard’s requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard’s requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard’s requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard’s requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard’s requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard’s requirements.
10.3 Degree of protection of ASSEMBLIES
Meets the product standard’s requirements.
10.4 Clearances and creepage distances
Meets the product standard’s requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder’s responsibility.
10.8 Connections for external conductors
Is the panel builder’s responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Is the panel builder’s responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder’s responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder’s responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder’s responsibility.
10.12 Electromagnetic compatibility
Is the panel builder’s responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.